Single Core V90HT 0.6/1KV

Single Core V90HT P.V.C. to AS/NZS 3191 0.6/1KV Voltage Rating

Applications: Wiring of Communication, Electronic Equipment and Switchboards
Conductor: Class 6 TINNED COPPER WIRE (TCW) to AS/NZS 1125
Insulation: RoHS Compliant V90HT P.V.C. to AS/NZS 3808 Colours: Black, Blue, Brown, Green / Yellow, Orange, Pink, Red, Grey, Violet, White, Yellow – Stripes available by request
Packs: 100, 500, 1,000 metres – other packs by request

CodeConductor
No. / Dia
(mm)
Nominal
Area
(mm²)
AMP
Rating
Insulation
Thickness
(mm)
Electrical
Resistance
at 20°C
(ohm/km)
Nominal
O.D.
(mm)
Mass
(kg/100m)
FVK1160216/0.200.550.840.12.61.1
FVK1240224/0.200.75120.826.72.81.4
FVK1320232/0.201170.82031.7
FVK13002530/0.251.5210.813.73.152.2
FVK15002550/0.252.5290.98.23.83.5
FVK1560356/0.304381.05.14.755.3
FVK1840384/0.36.0491.03.25.37.5
* Maximum operating temperature: 75°C in normal Use OR 105°C where not subject to, or protected from, mechanical damage (refer AS/NZS 3008.1.1:2009)
* AMP Ratings are to AS/NZS 3008. Unenclosed-Spaced at 40°C (in air), 25°C (in ground). Refer AS/NZS 3008 for derating factors.
* Tycab holds current independent compliance review report on PVC Cable compliance for GREEN STAR PVC Credit