CODE | NO. OF CORES | NOMINAL AREA (mm²) | CONDUCTOR NO/DIA (mm) | INSULATION THICKNESS (mm) | SHEATH THICKNESS (mm) | NOMINAl O.D. (mm) | MASS (kg/100m) |
BED3705 | 2C+E | 1.5 | 7/0.5 | 0.6 | 0.9 | 4.6 x 9.9 | 8.9 |
BED37067 | 2C+E | 2.5 | 7/0.67 | 0.7 | 1.0 | 5.5 x 12.2 | 14 |
CURRENT RATING | ELECTRICAL CHARACTERISTICS | ||||
Unenclosed In Air | Completely surrounded by thermal insulation | Unenclosed partially surrounded by insulation | Electrical Resistance @ 20°C (ohm/km) | Single Phase Voltage Drop mV/Am at 75°C Laid Flat | Three Phase Voltage Drop mV/Am 75°C Laid Flat |
15 | 8 | 12 | 13.6 | 33.03 | 28.6 |
22 | 11 | 17 | 7.4 | 18.02 | 15.6 |
** Electrical Product Safety Certification (EPSC) Scheme
** Certificate Number: AZ 69026878
** Authorised Marking: TUV-026878-EA
Tyree Cable has been examined and found to be in conformity with the requirements of the Best Practice Guidelines for PVC in the Built Environment 10/8/2010 Green Star PVC Credit utilising Auditor Verification Guidance Issue 2 20th November 2013.
Certificate number: 4069